01
Check the EPA date and New York requirements together
As of November 18, 2026, EPA lists a global warming potential (GWP) limit of 700 and January 1, 2027 for data-center, computer-room and IT-equipment cooling. For a self-contained product, the table applies to manufacture or import. For a new field-assembled system, the table applies to installation. An owner deciding whether to repair an operating unit is asking a third question.
New York’s Part 494 separately sets data-center restrictions using 20-year GWP (GWP20), including an earlier date than the federal 2027 entry. The federal date therefore does not establish that a New York project may proceed. DEC’s October 2026 FAQ says federal changes and extensions are not automatically adopted. Have a qualified professional confirm the equipment and end-use classification, proposed activity and any applicable exemption or DEC variance before ordering. This is not a universal deadline to replace existing CRAC equipment.
Put the project address, equipment classification, proposed work and expected manufacture or installation date at the top of the quote review. Ask the supplier to identify the applicable rule and any exception it relies on. For a Northern New Jersey installation, have the project team check New Jersey requirements for that address alongside the federal table. New York Part 494 applies in New York.