Which HVAC efficiency rating should you compare?
SEER2 describes seasonal cooling efficiency for applicable unitary equipment; EER2 describes efficiency at stated rating conditions. IEER combines full- and part-load ratings for applicable commercial unitary equipment. IPLV is a weighted chiller part-load metric. Compare like equipment using the same metric, units and rating basis. These ratings do not directly predict a building's utility bill or establish available capacity at every condition.
Match the metric to its equipment and purpose
The table is a reading guide for common rating documents, not a complete catalog of equipment standards. Special categories can use other metrics. Record the actual standard and edition on the proposal or certificate; do not assume every system installed on a roof or in a computer room belongs to the same category.
| Metric | Common equipment context | What it summarizes | Direction within a valid comparison |
|---|---|---|---|
| SEER2 | Applicable residential and small unitary air conditioners / heat pumps | Seasonal cooling output per electrical energy under the test procedure | Higher Btu/Wh indicates higher rated efficiency |
| EER2 | Applicable unitary air conditioners / heat pumps | Cooling capacity divided by electrical power at stated rating conditions | Higher Btu/Wh indicates higher rated efficiency |
| IEER | Applicable commercial unitary air conditioners / heat pumps | Weighted efficiency at specified full- and part-load conditions | Higher Btu/Wh indicates higher rated efficiency |
| IPLV | Applicable water-chilling packages | Weighted chiller part-load performance at standard conditions | Lower kW/ton or higher COP/EER indicates higher rated efficiency |
SEER2 and EER2 answer different cooling questions
AHRI 210/240-2024 defines SEER2 using seasonal heat removal and electrical energy consumption. EER2 relates cooling capacity to electrical power at a given set of rating conditions. The seasonal number and the point-condition number can both appear on the same system's documentation; they should not be ranked against each other as though they were one test.
Keep the full metric name. A proposal labeled SEER and one labeled SEER2 do not provide a clean like-for-like comparison. Request the appropriate comparable documentation rather than applying an assumed universal conversion factor. For a split system, retain the proposed indoor/outdoor combination with the rating.
Cooling efficiency also does not answer the heating-performance question for a heat pump. Review its separate heating capacity and efficiency data against the intended conditions when evaluating that part of the proposal.
IEER and IPLV are weighted comparisons
AHRI 340/360-2022 calculates IEER using ratings at 100%, 75%, 50% and 25% load with specified conditions and weighting. It gives a broader part-load comparison than a single full-load EER. It is still a standardized result, not a measured annual efficiency for your building.
AHRI 550/590-2023 describes IPLV as a chiller comparison metric and explicitly cautions against using it alone to predict annual energy use or savings. Chiller-plant energy also depends on operating conditions and other equipment. Read whether the value is expressed in kW/ton, COP or EER; the favorable direction changes with the unit.
A chiller submittal may also show application data or a nonstandard part-load value. Keep those labels and conditions intact. Do not relabel an application selection as a standard IPLV or compare unlike conditions without the appropriate technical review.
Practice reading three labeled example records
The following are invented document-reading examples, not real certificates, product recommendations or Airplex performance results. They show what to retain when copying values from actual documents. The blank worksheet below is for your own selections.
In a separate arithmetic example, 36,000 Btu/h of cooling divided by 3,000 W of input gives an EER-type ratio of 12 Btu/Wh at that stated condition. It does not become a SEER2 rating. Likewise, a hypothetical 100-ton duty at 0.65 kW/ton implies 65 kW at that same point, not a yearly consumption forecast.
| Example document | Stated information | Useful reading | Still needed |
|---|---|---|---|
| A: matched-system certificate example | SEER2 16.0; EER2 11.0 | Two different metrics for the same assumed combination | Actual model identifiers, certificate and edition |
| B: commercial unitary rating example | EER 11.0; IEER 15.0 | Full-load and weighted part-load evidence differ | Exact configuration, capacity and rating conditions |
| C: chiller selection example | Full-load 0.65 kW/ton; IPLV 0.40 kW/ton | Part-load and full-load values cannot be substituted for each other | Standard/application basis and complete selection |
Resolve mismatched evidence before ranking proposals
Place the two selections side by side. Confirm equipment category, capacity basis, complete model combination, metric, units and standard edition. If one proposal supplies only a family brochure while the other supplies a selected-model certificate, request the missing selected-model evidence before treating the values as comparable.
Then keep the efficiency comparison separate from fit: capacity at the required conditions, distribution, electrical requirements, controls and installation constraints still need review. A favorable rating cannot cure a mismatch with the building's duty.
The worksheet records the evidence and open comparison question. It does not score products or predict savings. For a government purchase, move the relevant rating evidence into the agency-specific register and link it to that purchase's requirement.
Put this guide to work
Equipment rating comparison worksheet
Use one column for each actual selection. Copy complete metric names, units and document identifiers; leave missing evidence unresolved. The examples above are not prefilled product data.
Open each item to add your notes, then download the CSV to keep a copy. This tool does not save or submit your entries; do not rely on your browser restoring them.
Equipment category and exact models
Rated capacity and conditions
Metric and complete unit
Full-load rating
Seasonal or part-load rating
Matched components / selected options
Certificate or selection revision
Required site-condition performance
Continue with a related decision
Questions & answers
Can I convert SEER2 directly into IEER or IPLV?
There is no general conversion that makes these different rating procedures equivalent. They use different equipment categories, conditions and weighting. Request the metric appropriate to the equipment and compare on that basis.
Is a lower IPLV number worse?
Check the unit. A lower kW/ton value means less electrical input per unit of cooling at that rating basis. For a COP or EER expression, a higher value indicates greater rated efficiency. Always preserve the units.
Does the highest rating guarantee the lowest bill?
No. The actual duty, climate, operating hours, controls, installation and other system energy uses affect consumption. A site-specific analysis is needed to estimate the financial outcome.
Sources & technical references
- AHRI 210/240-2024 (I-P) — Unitary Air-conditioning and Air-source Heat Pump Equipment
Official edition selector: choose the 2024 (I-P) download for definitions 3.2.18 (EER2) and 3.2.53 (SEER2). The page also lists a 2026 edition. This guide uses the named dated reference to explain the metrics, not to determine which edition governs a purchase.
- AHRI 340/360-2022 (I-P) — Commercial and Industrial Unitary Equipment
Official edition selector linking the 2022 (I-P) standard. Section 6.2.2 explains the IEER load points, conditions and weighting used in this guide. Retain the edition stated on the actual equipment documentation.
- ANSI/AHRI 550/590-2023 (I-P) — Water-Chilling and Heat Pump Water-Heating Packages
Official edition selector: choose the 2023 (I-P) download for Appendix D on IPLV purpose, unit relationships and limits on predicting site energy savings. The page also lists newer editions; this guide's dated example does not determine the edition applicable to a project.
- AHRI — 2023 Energy Efficiency Standards
Explains the change in residential rating metrics and test procedure. Used for the distinction between older and newer labels, not current minimum-efficiency advice.
NYC & Northern New Jersey
Compare the documents before the headline numbers
Bring the exact proposed models, rating documents and building requirements to an Airplex Mechanical equipment-scope discussion. Identify both the efficiency question and the duty the equipment must serve.