Water flow calculation

Chilled-Water Flow Calculator: Cooling Load, Delta T and GPM

Turn a stated cooling load and water temperature difference into an estimated flow. Keep the load, fluid and measurement boundary attached to the result.

Airplex Mechanical resources Reviewed November 16, 2026

Start here

How much chilled water does a stated load require?

Water flow depends on the heat carried and the temperature rise across the load. For the same cooling load, a smaller temperature difference requires more flow. This calculator estimates that thermal relationship using approximate water properties. It does not measure actual flow, establish the building load or select a pump, pipe or chiller.

Interactive planning tool

Work through your numbers

Example inputs are prefilled. Change them to match your measurements. Results stay in this browser and are not submitted to Airplex.

Choose your inputs, then calculate.

Choose inputs that describe the same duty

Use the thermal load assigned to the water circuit you are reviewing. A chiller's electrical input, a whole-building load and one coil's cooling duty are different quantities. For a liquid-cooled IT application, establish which heat is actually transferred into this water loop before entering the load.

Delta T is a difference, not a supply-water setpoint. A supply temperature of 7°C and return of 12°C gives a 5°C difference. The same difference is 9°F; temperature intervals convert by a factor of 1.8 without adding 32. Do not pair a peak load with an unrelated low-load temperature reading.

Input check before calculation
InputUseKeep with the result
Cooling loadThermal kW or the displayed cooling-load unitLoad source and operating condition
Water delta TPositive return-minus-supply difference across the loadMeasurement locations and units
FluidLiquid water approximationConfirmation that glycol or another coolant is absent

The calculation and its assumptions

The heat balance is Q = mass flow × specific heat × delta T. With water density approximated as 1 kg/L and specific heat as 4.184 kJ/(kg·K), flow in L/s = cooling load in kW ÷ (4.184 × delta T in °C). Multiply L/s by 15.8503 to obtain US gallons per minute.

Trane's Chilled-Water Systems training reference presents this relationship and explains that its water factor depends on density and specific heat. The familiar imperial shortcut, load in Btu/h ≈ 500 × US GPM × delta T in °F, uses rounded properties. Small differences between calculators can come from rounding or the assumed water temperature.

Use a positive load and positive delta T. A zero temperature difference cannot produce a finite flow result for a positive load. If the real readings show that condition, review the measurements and operating state before using the calculation.

References: [1]

Example: 100 kW with a 5°C water rise

This is a hypothetical calculation, not an Airplex project result. At 100 kW and a 5°C delta T, estimated flow is 100 ÷ (4.184 × 5) = 4.78 L/s, or about 75.8 US GPM.

Keeping that load fixed and reducing delta T to 2.5°C doubles the calculated flow to about 151.5 US GPM. This shows the relationship between the inputs. It is not an instruction to change the system's flow or temperature settings.

Illustrative input comparison
Cooling loadWater delta TEstimated US GPM
100 kW5°C / 9°F75.8
100 kW2.5°C / 4.5°F151.5

What to do with the result

Record the result beside the source load, fluid description and temperature basis. Compare it with the equipment's approved operating data and the relevant measured flow or design schedule. A disagreement is a question for review; the arithmetic alone cannot identify a valve, sensor, coil or pump fault.

Pump selection also requires the system's hydraulic resistance and operating arrangement. Pipe selection, minimum chiller flow, control stability and equipment limits require their own assessment. For a glycol blend, use its concentration- and temperature-specific properties instead of treating the water estimate as an approved design.

Continue with a related decision

Questions & answers

Does this calculate the cooling load?

No. It converts a load you supply into estimated water flow at the stated temperature difference. Establish the circuit's load separately; installed nameplate capacity does not prove the current operating load.

Can I use this result to order a replacement pump?

No. Flow is only one input to pump selection. Hydraulic resistance, the existing arrangement, equipment limits and control requirements also matter. Bring the result and its assumptions to the system review.

Sources & technical references

  1. Trane — Chilled-Water Systems, January 2021, page 24

    Heat-balance method, approximate water properties and fluid-property limitations. Technical reference, not site design approval.

NYC & Northern New Jersey

Bring the calculation with its assumptions

For a building or facility in NYC or Northern New Jersey, share the equipment, fluid, load source and temperature readings when discussing chiller or water-system service with Airplex Mechanical.

Discuss the water-system scopeCall (347) 627-7146
Call Now Request Service