Start here
What power does a supplied pump duty represent?
Hydraulic output is P = ρgQH, expressed here in kW after unit conversion. If pump efficiency is supplied, dividing hydraulic output by that efficiency estimates mechanical input at the pump shaft. The result does not select a pump or motor, and it does not report electricity consumption.
Interactive planning tool
Work through your numbers
Example inputs are prefilled. Change them to match your measurements. Results stay in this browser and are not submitted to Airplex.
Identify flow, total head and fluid
Enter volume flow in liters per second or US gallons per minute, then total head in meters or feet of the pumped liquid. Total head is the energy increase per unit weight across the pump; it is not automatically the building height or a single discharge-pressure reading.
Use the duty stated on an applicable selection or a qualified measurement record. Flow and head need to describe the same operating point. A design flow combined with a shutoff head represents neither that design point nor the actual installed duty.
Density is in kg/m³. A default of 1,000 kg/m³ is a convenient water-like example, not a measurement of every hydronic fluid. Use documented density at the relevant temperature and concentration for a glycol mixture or other liquid. Density alone does not model viscosity effects on pump performance.
Keep the three power boundaries separate
The Hydraulic Institute's formula reference gives hydraulic power in kW as ρ × g × Q × H ÷ 1,000, with density in kg/m³, flow in m³/s and head in meters. This tool uses g = 9.81 m/s². It converts L/s by dividing by 1,000, US GPM using 0.003785411784 m³ per US gallon and 60 seconds per minute, and feet using 0.3048 m per foot.
Pump shaft input is hydraulic output divided by pump efficiency as a decimal. Enter 70 for 70%; the calculation uses 0.70. The relevant efficiency belongs to the pump at the selected duty, rather than a motor efficiency or a generic best-efficiency-point value.
The Institute distinguishes pump efficiency from overall efficiency based on electrical input to a motor or drive. This calculator stops at shaft power and deliberately has no electrical-input output.
| Quantity | Boundary | Evidence needed |
|---|---|---|
| Hydraulic output | Power transferred to liquid | Flow, total head and fluid density |
| Pump shaft input | Mechanical power entering pump | Hydraulic output and applicable pump efficiency |
| Electrical input | Power entering motor or drive | Separate efficiency or electrical evidence; not calculated |
References: [1]
Worked example: 10 L/s at 20 m head
For a hypothetical flow of 10 L/s, total head of 20 m and density of 1,000 kg/m³, convert flow to 0.010 m³/s. Hydraulic power is 1,000 × 9.81 × 0.010 × 20 ÷ 1,000 = 1.962 kW.
At 70% pump efficiency, shaft input is 1.962 ÷ 0.70 = 2.803 kW, rounded. If the efficiency field is left blank, only the 1.962 kW hydraulic result is justified. Filling the blank with 100% would create an unsupported idealized shaft estimate.
At the same flow and head but density of 1,050 kg/m³, hydraulic power becomes 2.0601 kW. This isolated arithmetic comparison does not prove how an actual pump's operating point or efficiency changes when its fluid changes.
Valid numbers do not select equipment
Flow and head must be zero or positive, and density must be greater than zero. Optional efficiency must be greater than zero and at most 100%. Blank flow, head or density needs correction; a blank efficiency is permitted. Zero flow or zero head returns zero hydraulic output.
Zero hydraulic output does not prove zero actual motor input. A running pump at zero delivered flow can still consume power, and a constant assumed efficiency is not a valid way to characterize every operating state.
Pump selection also requires the actual curve, operating range, fluid compatibility, available suction conditions, cavitation review, control strategy and mechanical constraints. This tool checks none of those. It cannot establish an acceptable motor size by rounding the calculated shaft result upward.
Preserve the duty with the result
Keep the curve or source record, its date, the fluid basis and the efficiency boundary with the calculation. If the real concern is low flow, unusual noise or repeated faults, include that observation in the service request. The calculated power is background for the investigation, not a diagnosis.
Questions & answers
Can I use pressure instead of head?
The form expects total head. Pressure-to-head conversion depends on liquid density, and total pump head can require velocity and elevation terms. Use a properly established duty rather than substituting a gauge value.
Why is shaft power higher than hydraulic output?
For an efficiency below 100%, mechanical input exceeds the useful hydraulic output. The difference represents losses within the pump at that duty.
Does this estimate kWh?
No. It does not calculate electrical input or operating hours. kW is power; electricity use over time requires an applicable electrical power profile.
Sources & technical references
- Hydraulic Institute: Pump System Certification Exam Formula Reference Sheet
Version 1, pp.5–6: density-based hydraulic power, pump input and overall-efficiency boundaries; earlier pages define head terms. Reviewed November 16, 2026.
NYC & Northern New Jersey
Bring the duty and the curve together
Share the installed pump identity, flow/head record and the concern that prompted the calculation. Airplex Mechanical can discuss a scoped pump or hydronic service review for your NYC or Northern New Jersey building.
Discuss a pump service needCall (347) 627-7146