How is log mean temperature difference calculated?
Calculate the hot-minus-cold temperature difference at each physical end of the exchanger, then use LMTD = (ΔT₁ − ΔT₂) ÷ ln(ΔT₁/ΔT₂). The pairing changes between parallel and counterflow. Equal positive terminal differences return that common value. The result is a temperature difference, not heat duty, area or equipment capacity.
Interactive planning tool
Work through your numbers
Example inputs are prefilled. Change them to match your measurements. Results stay in this browser and are not submitted to Airplex.
Pair the streams at each physical end
Use hot-stream inlet and outlet and cold-stream inlet and outlet, all in the same scale. In parallel flow both streams enter at the same end. In counterflow they enter from opposite ends, so the hot inlet is paired with the cold outlet.
The DOE Mechanical Science handbook illustrates both arrangements and works the two pairings explicitly. Identify the arrangement from the equipment documentation. Pipe proximity, a drawing's left-to-right appearance or the word plate does not establish the internal flow configuration.
| Arrangement | First end, ΔT₁ | Second end, ΔT₂ |
|---|---|---|
| Parallel | Hot inlet − cold inlet | Hot outlet − cold outlet |
| Counterflow | Hot inlet − cold outlet | Hot outlet − cold inlet |
References: [1]
Method and the equal-difference limit
For positive, unequal terminal differences, LMTD = (ΔT₁ − ΔT₂) / ln(ΔT₁/ΔT₂), where ln is the natural logarithm. Reversing the labels of the two ends leaves the answer unchanged because both numerator and denominator change sign.
When both positive differences equal d, the direct expression appears as 0/0. Its continuous mathematical limit is d, which the calculator uses. This follows by writing one difference as d + x: x/ln(1 + x/d) tends to d as x tends to zero. It is a limit of the formula, not a separate exchanger rating rule.
The idealized method assumes an appropriate steady two-stream model. Spirax Sarco discusses constant specific heat, constant overall heat-transfer coefficient and neglected heat loss in its explanation. Actual multipass or crossflow configurations may need correction factors or a different model; those are not calculated here.
Worked example: equal ends and a parallel comparison
Consider hypothetical counterflow temperatures: hot fluid 80°C in and 60°C out; cold fluid 20°C in and 40°C out. The two end differences are 80 − 40 = 40°C and 60 − 20 = 40°C. The equal-difference limit gives LMTD = 40°C.
Using the same four temperatures in a parallel arrangement gives end differences of 60°C and 20°C. LMTD = (60 − 20)/ln(60/20) = 36.41°C, rounded. This is a comparison of specified temperature records, not a claim that reversing an installed exchanger will preserve its outlet temperatures.
The result describes the temperature driving force only. It does not establish heat duty without the applicable conductance and area or an independent fluid heat balance. A larger LMTD by itself does not prove that one installed exchanger is better.
Why counterflow outlet crossing can be valid
A second hypothetical counterflow case has hot fluid cooling from 80°C to 40°C and cold fluid warming from 20°C to 60°C. The cold outlet, 60°C, exceeds the hot outlet, 40°C. Those outlets are at opposite ends.
At the first physical end, 80 − 60 = 20°C; at the second, 40 − 20 = 20°C. Both driving differences are positive and LMTD is 20°C. The DOE handbook explicitly identifies this possible counterflow behavior. The same temperatures would be rejected in parallel flow because its outlet-end difference would be negative.
References: [1]
What the calculator accepts and what needs review
The hot stream must not warm, and the cold stream must not cool, in the modeled direction of heat transfer. Constant stream temperatures are permitted mathematically, but the calculator does not verify a phase-change process. Both calculated terminal differences must be strictly positive. Blank or nonfinite inputs, reverse temperature directions and zero or negative terminal differences need correction or a different model.
Subzero Celsius readings are not inherently invalid; the fluid must actually remain in its intended state. This tool does not determine freezing, boiling, phase change, fluid properties, pressure limits or whether the four temperatures satisfy a real flow-and-energy balance.
Near-equal differences need numerically stable handling, while very small end differences make input accuracy important. Keep sensor locations and timestamps with the record. A clean calculation cannot resolve an inaccurate sensor or temperatures collected during a changing load.
Continue with a related decision
Questions & answers
Is LMTD the hot-side water delta T?
No. A stream delta T compares that stream's own inlet and outlet. LMTD combines the hot-to-cold differences at the two physical ends of the exchanger.
Can I use this for a multipass exchanger?
Only as an explicitly idealized reference. Obtain the applicable manufacturer or designer model and correction method for the actual arrangement.
Does an LMTD result identify fouling?
No. Fouling assessment needs applicable baseline performance, flow, temperatures, fluid conditions and other evidence. LMTD alone does not isolate a fault.
Sources & technical references
- DOE Fundamentals Handbook, Mechanical Science, Volume 1: Heat Exchangers
DOE-HDBK-1018/1-93, January 1993, ME-02 pp.4–8: flow arrangements, outlet crossing, equation 2-1 and explicit terminal-pair examples. Engineering relationship, not a current design standard. Reviewed November 16, 2026.
- Spirax Sarco: Heat Transfer, section 2.5
Text following equation 2.5.5 states constant-property/coefficient and no-heat-loss assumptions. DOE supplies independently verified equation and liquid-stream pairing. Reviewed November 16, 2026.