Humidity calculation

Dew-Point Calculator: Temperature, Humidity and Condensation Risk

Calculate an approximate dew point from an air-temperature and relative-humidity reading. An optional surface comparison helps frame one local condensation question.

Airplex Mechanical resources Reviewed November 16, 2026

Start here

What does the calculated dew point tell you?

Dew point is the temperature at which the entered air would reach saturation when cooled at constant pressure without changing its moisture content. A surface at or below that temperature can support condensation. A warmer entered surface does not establish that the room, equipment or building is free of moisture problems; conditions and other surfaces may differ.

Interactive planning tool

Work through your numbers

Example inputs are prefilled. Change them to match your measurements. Results stay in this browser and are not submitted to Airplex.

Choose your inputs, then calculate.

Pair the measurements before calculating

Enter dry-bulb air temperature and relative humidity from the same location and observation. Avoid pairing a wall thermostat's temperature with humidity from a distant sensor. Record when the reading was taken and whether the system or nearby door conditions had just changed.

Relative humidity must be greater than 0% and no more than 100%. A logarithmic approximation cannot evaluate exactly 0% RH. The intended indoor screening range for this tool is air temperature from 0°C to 50°C, equivalent to 32°F to 122°F. That operating range is a tool boundary, not a comfort recommendation.

If you have a measured surface temperature, enter it in the selected temperature unit. Keep its location and time attached to it. A pipe surface, insulation surface and room-air reading are different measurements.

The Magnus approximation used here

With T in °C and RH in percent, calculate gamma = ln(RH ÷ 100) + 17.625 × T ÷ (243.04 + T). Dew point in °C = 243.04 × gamma ÷ (17.625 − gamma). Convert a Fahrenheit air input to Celsius before using the formula, then convert the resulting dew point back if required.

The coefficients are from the August-Roche-Magnus relationship published in EPA's humidity algorithm documentation, rearranged to solve for dew point. NOAA also publishes humidity and dew-point calculation references; different approximations can give slightly different answers.

This is an approximate liquid-water dew point, not a frost-point calculation. If the output is below freezing, it still uses the water relationship and should not be read as the temperature of ice deposition. The tool does not include a pressure correction or quantify sensor uncertainty.

References: [1] [2]

Example: 24°C air at 50% RH

For a hypothetical reading of 24°C and 50% RH, the calculation gives a dew point of about 12.9°C, or 55.3°F. A measured surface at 10°C would be about 2.9°C below that calculated dew point. That comparison supports investigating condensation conditions at that location.

A surface at 16°C would be about 3.1°C above the same calculated dew point. That one comparison does not rule out colder hidden surfaces, later humidity changes, a leak or a measurement error. No universal safety margin is assigned here.

Hypothetical surface comparisons for the same air reading
Air readingSurface readingCalculated comparison
24°C / 50% RH10°C2.9°C below dew point
24°C / 50% RH16°C3.1°C above dew point

Keep the calculation separate from diagnosis

Save the input readings and the result together. If visible moisture is the concern, also record its location, timing and what was observed. The calculation cannot distinguish condensation from a piping leak, drainage issue or another moisture source.

For a critical room, keep any equipment and control changes within the site's established review process. For a home or commercial space, use the result to request an appropriate investigation. Do not choose a humidity or cooling setpoint from this number alone.

Continue with a related decision

Questions & answers

Why can RH rise even if the moisture content has not changed?

Relative humidity depends on temperature. Cooling the same air can raise its RH without adding moisture. Use a paired temperature/RH reading to calculate dew point; the existing humidity guide explains the operating context in more detail.

Does a surface above the calculated dew point prove condensation cannot occur?

It describes only the entered measurements and approximation. Other surfaces, sensor error and changing conditions remain relevant. The result is not a diagnosis or clearance to operate equipment.

Sources & technical references

  1. US EPA — HMS Meteorology: Humidity Algorithms

    Published August-Roche-Magnus relationship with coefficients 17.625 and 243.04; algebraically inverted by this calculator.

  2. NOAA/NWS — Dewpoint and Wet-bulb from Relative Humidity

    Primary humidity-calculation reference with a linked formula document. NOAA's formula is a separate approximation, not the source of this tool's coefficients.

NYC & Northern New Jersey

Share the readings and the observed condition

Tell Airplex Mechanical whether the concern is in a home, commercial space or critical room, and include the measurement locations and visible symptoms when requesting an assessment.

Discuss the humidity concernCall (347) 627-7146
Call Now Request Service