HVAC CALCULATION REFERENCE

Sensible Cooling Airflow Calculator: Heat Load and Temperature Difference

Translate a supplied sensible heat load into an airflow estimate, with the air temperature difference and density assumption visible.

Airplex Mechanical resources Reviewed November 16, 2026

Start here

How much airflow carries a specified sensible heat load?

At the standard-air approximation used here, CFM = sensible Btu/h ÷ (1.08 × temperature difference in °F). This is the air volume needed to carry the entered temperature-related heat under those assumptions. It does not calculate the load itself or establish outdoor-air, filtration, humidity-control or equipment-selection requirements.

Interactive planning tool

Work through your numbers

Example inputs are prefilled. Change them to match your measurements. Results stay in this browser and are not submitted to Airplex.

Choose your inputs, then calculate.

Choose inputs from the same boundary

Enter the sensible heat rate in Btu/h or thermal kW. If a report includes both sensible and latent cooling, use its sensible portion. Latent cooling concerns moisture removal and is not represented by this equation. A model number or nominal tonnage is not a substitute for a documented sensible load.

The temperature difference is a positive difference in air temperatures, not a water-loop difference and not simply the outdoor temperature minus the thermostat setting. Identify the two air locations represented by your load calculation. Mixing a coil load with room-only temperatures can make a neat calculation describe the wrong boundary.

Record where the inputs came from: a design report, selected equipment performance, synchronized measurements or an explicitly hypothetical scenario. Keep those categories separate when discussing the result. A calculated airflow based on assumed temperatures does not become a measured airflow.

Method, units and the 1.08 factor

The underlying relationship is sensible heat rate = mass flow × specific heat × temperature difference. Thermotek's technical note explains the standard-air factor: 0.24 Btu/(lb·°F) × 0.075 lb/ft³ × 60 minutes/hour = 1.08. This calculator holds those properties fixed; temperature, pressure and altitude can change actual air density.

For kW input, the calculator converts thermal kW to Btu/h using approximately 3,412.142 Btu/h per kW. A Celsius temperature difference is multiplied by 1.8; adding 32 would be incorrect because this is a difference. The airflow conversion is approximately 0.471947 L/s per CFM.

The displayed precision describes the arithmetic, not the certainty of the input. If a heat-load estimate is rounded or the temperature difference changes during operation, preserve that context rather than reporting the output as an exact field requirement.

References: [1]

Worked example: 21,600 Btu/h across 20°F

This hypothetical case uses a sensible load of 21,600 Btu/h and an air temperature difference of 20°F. The denominator is 1.08 × 20 = 21.6. Dividing 21,600 by 21.6 gives 1,000 CFM, equivalent to about 471.95 L/s.

At the same sensible heat rate, changing the assumed difference to 10°F doubles the estimate to 2,000 CFM. That comparison explains sensitivity to an assumption; it does not authorize changing a supply temperature or fan setting. The equipment and distribution system must support any proposed operating condition.

Illustrative sensitivity at the same supplied sensible load
Sensible loadAir differenceCalculated airflow
21,600 Btu/h20°F1,000 CFM
21,600 Btu/h10°F2,000 CFM
21,600 Btu/h25°F800 CFM

What a valid result does and does not establish

The load must be zero or positive, and the temperature difference must be greater than zero. Blank inputs and negative loads are not meaningful substitutes for missing evidence. A zero load returns zero heat-transfer airflow mathematically; the building may still need ventilation, pressurization or circulation.

A very small positive temperature difference produces a very large airflow. Review the measurement boundary and input uncertainty before treating that result as useful. This tool does not model leakage, bypass, fan pressure capability, coil performance, latent heat, altitude correction or actual air distribution.

Total supply airflow and outdoor airflow answer different questions. Even when the same fan moves both, this heat-transfer calculation does not establish how much outside air or equivalent clean air a space needs. Use the ACH and duct-velocity tools for their separate arithmetic, and obtain the appropriate design basis for ventilation.

Bring the assumptions to the review

Save the heat-load source, the two air locations, temperature difference and output together. When a proposed fan or air handler is being compared, ask for its selected airflow and pressure condition and how those relate to the intended duty. A discrepancy is a review question, not proof of a failed blower.

Questions & answers

Can I enter electrical kW?

Only when a documented heat balance establishes that the entered electrical power becomes sensible heat within the chosen boundary. Otherwise use the sensible thermal load from the appropriate report. This calculator does not infer heat release from an equipment nameplate.

Does this size an air conditioner?

No. Equipment selection also needs total and latent duties, selected operating conditions, distribution requirements and manufacturer performance. The result is one heat-transfer relationship.

Why is this different from an ACH result?

ACH relates airflow to room volume. This calculator relates airflow to sensible heat and an air temperature difference. Neither output automatically specifies required outdoor ventilation.

Sources & technical references

  1. Thermotek: BTU calculation based on actual air density

    One-page technical note; specific heat, density, 1.08 factor and actual-density limitation. Reviewed November 16, 2026.

NYC & Northern New Jersey

Connect the estimate to the equipment

For an NYC or Northern New Jersey building, share the equipment identity, source of the heat-load figure and the airflow question. Airplex Mechanical can discuss the air-handler or blower service scope and the records needed for a useful review.

Discuss an airflow concernCall (347) 627-7146
Call Now Request Service