Duct airflow calculation

Duct Air Velocity Calculator: CFM and Round or Rectangular Ducts

Convert a stated airflow and internal duct dimensions into average velocity. Use the result to review an airflow record or prepare a more specific ductwork question.

Airplex Mechanical resources Reviewed November 16, 2026

Start here

How do CFM and duct size determine air velocity?

Average velocity is airflow divided by the duct's cross-sectional area. Divide CFM by square feet to obtain feet per minute. Round and rectangular ducts need different area calculations, but the flow relationship is the same. The result describes an average across the entered section; it does not select the duct or certify its noise, pressure loss or delivered airflow.

Interactive planning tool

Work through your numbers

Example inputs are prefilled. Change them to match your measurements. Results stay in this browser and are not submitted to Airplex.

Choose your inputs, then calculate.

Identify the section the airflow passes through

Choose round or rectangular and enter the clear internal dimensions in inches. A round input is diameter, not radius. For a rectangular section, use width and height; their order does not affect the area. Lining or internal obstructions can change the actual air passage.

Use the airflow through that section. A main duct upstream of several branches and one branch downstream do not normally carry the same flow. Note whether the CFM is a measured value, a design schedule value or an estimate. The calculator cannot resolve a mismatch between the record and the physical location.

Dimension and airflow checks
RecordConfirmCommon mix-up
Round ductInternal diameter in inchesEntering radius as diameter
Rectangular ductInternal width and height in inchesUsing outside insulated dimensions
AirflowCFM at this section and conditionUsing the full fan flow for a branch

Area first, then average velocity

For a round duct: area in ft² = π × diameter² ÷ 576, when diameter is in inches. For a rectangular duct: area in ft² = width × height ÷ 144, with both dimensions in inches. Average velocity in FPM = airflow in CFM ÷ area in ft².

TSI's application note LC-127 presents the flow, velocity and area relationship and both area equations. This calculator uses those geometric relationships without adopting that note's product-specific damper selection recommendations.

Dimensions must be greater than zero. Zero airflow produces zero calculated average velocity. Very small entered dimensions can create very large results; first check the units and the duct section before treating an unusual result as a system finding.

References: [1]

Example: the same CFM through two different areas

At an illustrative 1,000 CFM, a round 12-inch duct has an area of π × 12² ÷ 576 = 0.7854 ft². Average velocity is approximately 1,273 FPM. A rectangular 24 × 12-inch duct has an area of 2 ft², giving 500 FPM at the same airflow.

These hypothetical sections are comparison examples, not recommended replacements for one another. Duct shape, fittings, length, available pressure, acoustics, leakage and connections still affect a real design.

Hypothetical geometric comparison at 1,000 CFM
Internal sectionAreaAverage velocity
12-inch round0.7854 ft²1,273 FPM
24 × 12-inch rectangular2.0000 ft²500 FPM

Separate calculated average velocity from a field reading

The value is an average over the cross-section. A single point reading near an elbow, damper or wall can differ from that average. If a report supplies velocity instead of CFM, check its measurement method and location before using it to infer the total airflow.

For a ductwork review, attach the section dimensions, its location on a sketch, the airflow source and the operating mode. Report a noise or comfort concern separately from the calculated number. That gives the reviewer a useful starting point without naming a fault from arithmetic alone.

There is no pass/fail velocity band here. A satisfactory velocity for one duct or use can be unsuitable elsewhere. Review the relevant system criteria before changing dimensions, fan settings or balancing devices.

Continue with a related decision

Questions & answers

Does this determine friction loss?

No. Friction and fitting losses require additional information such as duct length, shape, roughness, fittings and air conditions. This tool calculates only area and average velocity from the supplied inputs.

Can I enter a grille's outside dimensions?

Do not treat the outside face dimensions as a verified free airflow area. A grille, louver or other device can have a different effective area and a manufacturer-specific measurement method. Use the appropriate product data for that task.

Sources & technical references

  1. TSI — Sizing Dampers, Application Note LC-127, Revision B (2012)

    Source for flow/area/velocity and round/rectangular area equations only; its damper recommendations are not universal design criteria.

NYC & Northern New Jersey

Connect the number to the actual duct section

Share the location, dimensions, airflow record and observed concern with Airplex Mechanical when discussing a ductwork or ventilation assessment.

Discuss the ductwork concernCall (347) 627-7146
Call Now Request Service