What changes when fan speed changes?
With a fixed fan geometry and air density at comparable operating points, the speed ratio r = N₂/N₁ scales airflow by r, pressure rise by r² and shaft power by r³. These are theoretical fan relationships. A real operating point depends on the system and controls, and shaft power is different from electrical input.
Interactive planning tool
Work through your numbers
Example inputs are prefilled. Change them to match your measurements. Results stay in this browser and are not submitted to Airplex.
Build one coherent baseline
Baseline speed, flow, pressure and shaft power must describe the same fan and operating point. A full-speed catalog airflow, a low-load pressure reading and a motor nameplate power are not a coherent baseline. Use an applicable selection sheet or a documented set of measurements.
The speed inputs are fan-shaft revolutions per minute. Motor RPM may differ where a transmission is present. A drive frequency alone is not the requested input. Use the static or total pressure-rise selector to preserve the same basis at both points; do not silently compare a fan total-pressure figure with external static pressure.
Enter flow in CFM, pressure rise in inches water gauge and shaft power in kW; these units are fixed in this calculator. The speed, flow, pressure and power ratios are dimensionless. Record the measurement or selection conditions alongside the input, especially if the value is an estimate.
The three relationships and their conditions
Let r = scenario RPM ÷ baseline RPM. Then Q₂ = Q₁r, Δp₂ = Δp₁r² and P₂ = P₁r³. Q is volume airflow, Δp is pressure rise and P is mechanical power at the fan shaft. DOE/AMCA presents these three speed relationships; Beckett Air's fan-law table expressly holds the impeller, system and density fixed.
The scenario assumes comparable operation of the same fan, with unchanged geometry and air density and approximately unchanged efficiency. It does not represent replacing a wheel, changing blade pitch, changing filters or dampers, or altering a pressure-control sequence.
DOE also explains why speed selection needs review of the load, airstream temperature and mechanical limits. Use the calculation to understand a scenario, then compare it with the manufacturer's permitted operating range and the actual system characteristic.
Worked example: 1,000 to 800 RPM
Take a hypothetical baseline of 1,000 RPM, 10,000 CFM, 1.5 inches water pressure rise and 5.0 kW shaft power. At 800 RPM the speed ratio is 0.8. The calculations give 8,000 CFM, 0.96 inches water and 2.56 kW shaft power.
The scenario therefore retains 80% of the baseline flow, 64% of its pressure rise and 51.2% of its theoretical shaft power. The arithmetic reduction in shaft power is 48.8%. It is not a bill reduction: operating hours, the actual duty, motor and drive efficiency, and controls are outside this tool.
For comparison, a ratio of 1.1 predicts 110% flow, 121% pressure and 133.1% shaft power. The different rates of change explain why a modest speed increase deserves a mechanical and electrical review.
| Speed ratio | Flow ratio | Pressure ratio | Shaft-power ratio |
|---|---|---|---|
| 0.8 | 0.8 | 0.64 | 0.512 |
| 1.0 | 1.0 | 1.0 | 1.0 |
| 1.1 | 1.1 | 1.21 | 1.331 |
Numerical limits and real-system limits
Both baseline and scenario RPM must be greater than zero for this rotating-fan similarity comparison. Baseline flow, pressure and power must be zero or positive. Missing values do not establish a baseline. Zero-speed behavior is outside this tool; windmilling, buoyancy flow or another fan driving air through the system need a different assessment.
The calculator does not check motor rating, shaft strength, vibration, minimum airflow, stall, sound, duct pressure limits or equipment temperature requirements. It also cannot guarantee that the actual system will move along the assumed comparable points. A mathematical result at a higher speed is not evidence that the fan can operate there.
Where a controls proposal includes savings, ask separately for the operating profile and electrical measurement or modeled basis. A cube-law comparison with one baseline point does not establish annual kWh or utility cost.
Turn the scenario into a useful question
Attach the calculation to the fan selection or test-and-balance record. State what needs resolution: an airflow shortfall, a proposed drive replacement or an unexplained power figure. Ask which assumptions match the installed system and which need verification before an authorized adjustment.
Questions & answers
Is shaft power the motor's nameplate rating?
No. A nameplate rating describes the motor's rated capability. The fan-law baseline needs the shaft power associated with the baseline duty; the two values are not interchangeable.
Can I use this to choose a drive frequency?
No. The tool accepts fan RPM and does not prescribe control settings. Equipment limits, transmission details, motor behavior and the approved sequence need a separate review.
Will reducing speed by 20% halve the electricity bill?
The model gives 51.2% of baseline shaft power at a speed ratio of 0.8. It does not calculate electrical input, run time or the building's other energy use.
Sources & technical references
- DOE/AMCA: Improving Fan System Performance
Engineering sourcebook, printed pp.4–5 and glossary: linear flow, square pressure, cube power and operating limitations; no historical economic figures used. Reviewed November 16, 2026.
- Beckett Air: Fan Laws
Manufacturer table explicitly fixes impeller, system and density for speed scaling. Reviewed November 16, 2026.