Cooling-Tower Range and Approach Calculator

Keep tower water temperatures and entering-air wet bulb together when interpreting a performance record.

Airplex Mechanical resources Reviewed November 16, 2026

Start here

What are cooling-tower range and approach?

Range is hot water entering the tower minus cold water leaving it. Approach is cold water leaving the tower minus the wet-bulb temperature of the entering air. Both are temperature differences. They describe the entered condition and cannot, on their own, certify tower capacity or establish a fault.

Interactive planning tool

Work through your numbers

Example inputs are prefilled. Change them to match your measurements. Results stay in this browser and are not submitted to Airplex.

Choose your inputs, then calculate.

Use the temperatures that belong to the tower

Hot water means the circulating water entering the tower; cold water means the water leaving it. Keep these separate from chilled-water supply and return on the evaporator side of a chiller. Labeling both systems supply and return without identifying the loop can reverse the intended calculation.

The air input is the wet-bulb temperature at the tower's entering-air condition. A rooftop dry-bulb sensor measures a different quantity. A weather-station wet bulb may also differ from the air actually entering a tower because of site conditions and recirculation.

Use the same °F or °C scale for all three temperatures. Retain the timestamp, sensor location and data source for each reading. If readings were taken at different loads or times, the subtraction is possible but the apparent operating condition may never have existed.

Range describes water cooling; approach references the air

Range = hot-water temperature − cold-water temperature. Approach = cold-water temperature − entering-air wet-bulb temperature. The ASHRAE cooling-tower chapter defines these quantities and explains that range depends on heat load and circulating water flow. Approach also depends on tower capability and the operating conditions.

A range or approach expressed as a °C difference has the same numerical value as a kelvin difference. A °F difference is 1.8 times the corresponding °C difference. Do not add 32 when converting a calculated difference.

These definitions are useful for reading a selection sheet or an operating log. They do not establish a universal target. The relevant comparison is the actual tower's documented performance at applicable load, flow, air condition and operating configuration.

References: [1]

Worked example: 95°F, 85°F and 78°F

For a hypothetical operating record of 95°F entering water, 85°F leaving water and 78°F entering-air wet bulb, range is 95 − 85 = 10°F. Approach is 85 − 78 = 7°F. In Celsius differences these are approximately 5.56°C and 3.89°C.

Now consider a second record: 90°F entering water, 82°F leaving water and 75°F wet bulb. Range is 8°F and approach remains 7°F. The colder leaving water alone does not prove improved tower performance; the entering air and water duty also changed.

The comparison supports a request for the missing flow, load and fan information. It does not establish that either condition is good, bad or equal in capacity.

Two hypothetical records, neither a certified test
RecordHot / cold / wet bulbRangeApproach
A95 / 85 / 78°F10°F7°F
B90 / 82 / 75°F8°F7°F

Read a warning as a reason to check the record

All inputs must be finite numbers on the selected common scale. Entering water below leaving water is inconsistent with the cooling direction modeled here. Equal water temperatures give zero range; that arithmetic does not establish why no difference was observed.

A zero or negative approach prompts review of inputs, timestamps, sensor locations and operating conditions. Do not turn it into a diagnosis of failed equipment or a claim of exceptional performance. Measurement uncertainty becomes especially significant when subtracting readings that are close.

No water chemistry, evaporation, blowdown, fan-power calculation or capacity correction is performed here. The separate water-balance tool addresses different inputs and cannot set treatment limits. A tower performance certification or field acceptance test needs the applicable procedure, instrumentation and qualified parties.

What to request with a performance claim

Ask the proposer or reviewer for the exact model, rating condition, water flow and heat duty associated with an approach claim. Record how many cells and fans were operating and whether the record is a selection, a field observation or a formal test.

For a shared building plant, identify which party holds the tower log and the chiller-side record. Preserve the original units and times in the handoff. The first useful action is often aligning the evidence before attributing a warmer-water complaint to the tower.

Continue with a related decision

Questions & answers

Is a smaller approach always better?

It indicates leaving water closer to the entered wet bulb, but a fair performance comparison also needs load, water flow, fan state and an applicable equipment rating. This tool does not rank towers.

Can I use a phone weather reading?

It is not automatically representative of tower entering air. Record its source if used for a rough scenario, and obtain the appropriate site measurement for a performance review.

Does a 10°F range prove the tower meets its duty?

No. Range is a temperature difference. Heat duty also requires flow and fluid information, while tower performance assessment needs the full operating condition.

Sources & technical references

  1. ASHRAE Handbook 2024, HVAC Systems and Equipment, Chapter 40: Cooling Towers

    Principle-of-operation definitions and performance-comparison sections; no universal approach threshold or field-test certification implied. Reviewed November 16, 2026.