Start here
How are tower make-up, blowdown and drift related?
At steady water level, make-up replaces evaporation and liquid losses. With no other losses, make-up = evaporation + blowdown + drift. Under the simplified dissolved-solids balance used here, deliberate blowdown = evaporation ÷ (cycles − 1) − drift. The result is a planning estimate for the supplied inputs, not a water-treatment setting or a savings commitment.
Interactive planning tool
Work through your numbers
Example inputs are prefilled. Change them to match your measurements. Results stay in this browser and are not submitted to Airplex.
Three inputs, each with a documented basis
Enter an evaporation rate from an appropriate calculation or established operating record, the documented cycles of concentration and the drift rate. Keep all rates in the calculator's displayed unit. If the records are daily totals, first put them on a common time basis; do not mix a peak-hour evaporation estimate with an average-day loss.
Cycles is a concentration ratio: dissolved-solids concentration in recirculating water compared with make-up water. DOE identifies conductivity comparison as an operating indicator and stresses the limits imposed by make-up quality and treatment. Enter a ratio greater than one. The example value on this page is not a recommended target.
| Input | Meaning | Review before use |
|---|---|---|
| Evaporation E | Water leaving as vapor | Source, load and time basis |
| Cycles C | Circulating-to-make-up concentration ratio | Treatment-approved basis and sample context |
| Drift D | Liquid droplets carried out of the tower | Documented rate or explicit assumption |
References: [1]
A steady-state water and dissolved-solids balance
The calculator uses B = E ÷ (C − 1) − D, then M = E + B + D. Here B is deliberate blowdown, M is make-up, E is evaporation, D is drift and C is cycles. It assumes steady operation, negligible dissolved solids in evaporated vapor and drift at the circulating-water concentration. Leaks, overflow and other liquid withdrawals are excluded.
The DOE tower fact sheet sometimes groups every non-evaporative loss under the word blowdown. This tool splits that total into deliberate blowdown plus drift. Its equivalent concentration relationship is C = M ÷ (B + D), under the assumptions above. This distinction prevents counting drift twice.
A calculated negative blowdown means the entered drift already exceeds the total liquid loss consistent with the selected evaporation and cycles. Those inputs do not fit this model. Do not interpret the result as a physical negative discharge or a direction to close a valve.
Example: 100 GPM evaporation and five cycles
For a hypothetical evaporation rate of 100 GPM, cycles of 5 and drift of 1 GPM, total non-evaporative loss is 100 ÷ (5 − 1) = 25 GPM. Subtracting drift gives deliberate blowdown of 24 GPM. Make-up is 100 + 24 + 1 = 125 GPM.
The check is 125 ÷ (24 + 1) = 5 cycles. If these rates remained constant for eight hours, make-up would be 60,000 US gallons. That is a time conversion of the example, not a forecast of an actual tower's daily consumption.
| Flow | Rate | Role |
|---|---|---|
| Evaporation | 100 | Input |
| Drift | 1 | Input |
| Deliberate blowdown | 24 | Calculated |
| Make-up | 125 | Calculated |
Compare the estimate with operating records
Record the assumptions beside meter totals and the treatment provider's information. A difference can point to missing losses, changing load, differing time periods or an input problem; the calculator cannot identify the cause. Do not assume the theoretical balance measures actual use.
Use this page to prepare a tower operating-review question. Mechanical condition, water treatment and the building's water-management responsibilities remain distinct work scopes. The tool does not assess biological risk, establish chemistry or prescribe treatment and blowdown changes.
Continue with a related decision
Questions & answers
Can the calculator choose the best cycles of concentration?
No. Suitable cycles depend on the actual make-up water, materials, treatment and operating conditions. Use the concentration basis established for the system and refer proposed changes to the responsible treatment specialist.
What if the tower has overflow or a known leak?
The simplified calculation excludes those losses. Record them separately and use a fuller water balance; otherwise the result may not reconcile with the make-up meter. Mechanical faults also need their own assessment.
Sources & technical references
- DOE FEMP — Best Management Practice #10: Cooling Tower Management
Water-loss categories, make-up balance, cycles and treatment limitations; checked November 16, 2026.
- DOE FEMP — Cooling Towers: Understanding Key Components and Water Efficiency
System-calculation equations and the convention that groups non-evaporative losses as blowdown. Used for physical relationships, not its historical policy statements.
NYC & Northern New Jersey
Bring meter records and the treatment context
Tell Airplex Mechanical which tower you are reviewing, what the water-use records show and which mechanical concern needs assessment. Keep treatment decisions with the responsible specialist.
Discuss the tower service scopeCall (347) 627-7146